Delta Electronics — 6.27.2 Explanation of CANopen Communication Instructions

AS Series Programming Manual 8. Set the relevant DI signal configuration parameters manually or with the COPRW instruction to modify the hardware DI signal setting of ASD-A2. Use COPRW to modify the configuration after execution of the INITC instruction is complete and before the servo is enabled. 9. When the initialization is complete, the servo is in the PR mode. Do not make any communication control on servo P5-18. 10. For more details on the servo parameters, refer to the Delta Servo Operation manual. Example of Communication with Delta Inverter 1.

Manually set the inverter parameter P09-36 (ranging from 21 to 28), P09-37 (communication baud rate default is 1MHz) and P09-40 to standard CANopen protocol (default). 2. Manually set the source of frequency command P00-20 to 6 and source of the operation command P00-21 to 3, and have them controlled by CANopen communication. 3. The following list shows the settings to initialize an inverter in the AS Series. A. Set PDO mapping area: the operation frequencies, current state, and states of torque and DI point correspond to PLC SRs. B. Set time for the heartbeat and the PLC scan overtime to 200ms (default).

When a communication overtime _6 occurs, PLC will send error message (error LED flashing slowly; refer to error code for more details) and the servo turns off automatically. 4. For more details on the servo parameters, refer to the Delta Inverter Operation manual. Example 1. When M0 changes from OFF to ON, the INITC instruction starts to initialize the inverter at station address 21, until SM1683 is ON. When SM1683 is ON, it indicates the initialization is complete. 6-898