Delta Electronics — 7.2.2 ERROR LED Indicators Blinking Every 0.5 Seconds

Chapter 7 Troubleshooting  Error Code: Error codes in the error log.  Date & Time: The date and time the error occurred. The most recently occurring error is listed on the top.  The last column shows the descriptions for the error. 7.2 Troubleshooting for CPU Modules Check the LED indicators and the error codes from the CPU module and refer to the following table for troubleshooting. V in the Log column indicates the error is recorded in the log. X in the Log column indicates the error is not recorded in the log. H in the Log column indicates whether or not you can set recording the error in the log in HWCONFIG.

7.2.1 ERROR LED Indicators Are ON 7.2.2 ERROR LED Indicators Blinking Every 0.5 Seconds 7_ 7-5 Error Code Description Solution Flag Log (16#) 000A Scan timeout 1. Check the setting of the watchdog timer in HWCONFIG. 2. Check whether the program causes a long scan time SM8 V Error Code Description Solution Flag Log (16#) 000C The program in the PLC is damaged. Download the program again. SM9 V 0010 CPU memory is denied. Contact your distributor. SM9 V 002E CPU external memory access is denied. Contact your distributor. SM9 V 002F PLC programs are not consistent with the system logs. Download the program again.

SM34 V 0070 The arrangement of the function cards is not consistent with the settings. Check whether the settings in HWCONFIG are consistent with the arrangement of the function cards. SM10 V 0102 The interrupt number exceeds the range. Check the program, compile the program again, and download the program again. SM5 X 0202 The MC instruction exceeds the range. Check the program, compile the program again, and download the program again. SM5 X 0302 The MCR instruction exceeds the range. Check the program, compile the program again, and download the program again. SM5 X 0D03 The operands used in DHSCS are not used properly.

Check the program, compile the program again, and download the program again. SM5 X 0E05 The operands HCXXX used in DCNT are not used properly. Check the program, compile the program again, and download the program again. SM5 X 1300 - 130F Errors occurred in the remote modules Refer to Section 7.3.4 for more information on the error codes for the remote modules. SM30 V