Chapter 2 Devices SR824 Hardware sending error counter for CAN communication: when the error number exceeds 127, it indicates the hardware error occurance is too frequent, you need to check the communication cables or adjust the transmission speed or modify the sample points manually. 18. Ethernet IP related flags SM1000, SR1000~SR1015, and (SR1536~SR1540 available for firmware V1.06.00 or later) 2_ 2-119 SM/SR Function Action SM1000 Ethernet setting flag. ON: the values in SR1000–SR1006 are written into the flash memory. After writing the values, the PLC resets it to OFF. NOTE 1: do not set the flag to ON continuously to avoid damage to the flash memory. NOTE 2:
the PLC must be in STOP state before writing the values into the flash memory. SR1000 Ethernet IP address (32-bit) For example: 192.168.1.5, SR1000 is 16#C0A8 and SR1001 is 0105. SR1001 SR1002 Ethernet netmask address (32-bit) For example: 255.255.255.0, SR1002 is 16#FFFF, and SR1003 is FF00 SR1003 SR1004 Ethernet gateway address (32-bit) For example: 192.168.1.1, SR1004 is 16#C0A8, and SR1005 is 0101 SR1005 SR1006 SR1007 SR1009 Duration of the TCP connection Current Ethernet speed Current TCP connection number Unit: second; default: 30 seconds; setting range:
1-32000; if the setting value exceeds the setting range, when When the value exceeds the range, the system treats the value as the minimum 1 or the maximum 32000. Unit: Mbps Number of all the TCP connections SR1010 Time to restart TCP communication Unit: ms; default: 20 ms; setting range: 0-32000; when the value exceeds the range, the system treats the value as the minimum 0 or the maximum 32000. If the setting value is 0, it indicates system restarts communication automatically. SR1011 MODBUS/TCP Server connection number The system is refreshed automatically. SR1012 MODBUS/TCP Client connection number The system is refreshed automatically.
SR1013 EtherNet/IP Adapter connection number The system is refreshed automatically. SR1014 EtherNet/IP Scanner connection number The system is refreshed automatically. SR1015 MODBUS/TCP Server packet receiving timeout Unit: ms; default: 10 ms; setting range: 0-32000; when the value exceeds the range, the system treats the value as the minimum 0 or the maximum 32000 SR1536 Current AS-FEN02 TCP connection number Number of all AS-FEN02 TCP connections SR1537 AS-FEN02 MODBUS/TCP Serves connection number The system is refreshed automatically. SR1538 AS-FEN02 MODBUS/TCP Client connection number The system is refreshed automatically.
SR1539 AS-FEN02 EtherNet/IP Adapter connection number The system is refreshed automatically. SR1540 AS-FEN02 EtherNet/IP Scanner connection number The system is refreshed automatically.