Delta Electronics — 2.2.16 Additional Remarks on Special Auxiliary Relays and Special Data Registers

Chapter 2 Devices  Error codes for Ethernet connections 2_  The list of SM/SR states when connecting to RTU-EN01 throught Ethernet port Note: Before the connection is established, it is suggested NOT to use data (RX/RY/RCR Read/RCR Write) in the mapping area. 21. When selecting “Manual + Flags” in “I/O allocation setting when Power On”, use flags SM230-SM261 to activate the 1 st – 32 nd module on the right-side of the CPU module. (available for FW V1.06.00 or later ) For less module applications, you can use the same PLC program and download the I/O allocation table once for various I/O applications. Two things to be noted when applying this mode: A.

You need to use a bigger I/O allocation planning beforehand and store this planning in AS series PLC. B. You can simply use special flags to mark which I/O module will NOT be used to meet the actual I/O module placement. But you cannot rearrange the original order of the module placement. Add a new selection “Manual + Flags” for the setting option “I/O module allocation setting when Power ON”. Select this option, you need to use it with flags SM230-SM261. For less module applications, you can simply use special flags to mark which I/O module will NOT be used to meet the actual I/O module placement.

In this mode, you can use the same PLC program and download the I/O allocation table once for various I/O applications.

2-123 Error code Description 16#00XX Remote module response error Code 1~7 are standard Modbus TCP protocol error codes 16#F000 Ethernet connection is not established 16#F001 Remote module response timeout 16#F003 TCP connection timeout 16#F007 Response error 16#F009 Connection lost in the remote module SM / SR Description SM1312 - SM1315 The communication state flags of RTU-EN01 connection ID 1-4 SR1312 - SR1315 The communication state codes of RTU-EN01 connection ID 1-4 SR SM state Description 0 Off Connection closed 1 On Successful connection 2 Off Communiction timeout 3 Off Connection closed by force 4 Off RTU-EN01 response: error in contents 5 Off RTU-EN01 response:

error 6 Off Network not connected or connection failed SM state RX & RCR Read data RY & RCR Write data (input mapping area) (output mapping area) Off  On Clear to 0 Clear to 0 On  Off No change No change