Delta Electronics — 6.13.2 Explanation of Data Processing Instructions

AS Series Programming Manual (D0+D1+D2)/3 D10 D0 100 D1 113 D10 After the instruction is executed 112 D2 125 The quotient 2 is left out. Additional remarks 1. For 16-bit instructions, if n not between 1–256, the instruction is not executed, SM0 is ON, and the error code in SR0 is 16#200B. 2. For 32-bit instruction, if n is not between1–128, the instruction is not executed, SM0 is ON, and the error code in SR0 is 16#200B. 3. If S + n -1 exceeds the device range, the instruction is not executed, SM0 is ON, and the error code in SR0 is 16#2003. _6 6-358