Delta Electronics — 6.15.2 Explanation of Module Instructions

Chapter 6 Applied Instructions Explanation 1. This instruction is available for PLC with FW V1.08.00 or later. 2. ATarPosi is the position for absolute addressing. The input pulse number is a signed 32 bit value. The PU module will automatically compare it with the present position. If the comparison result is greater than 0, the output will be conducted in the positive direction (and the direction output point is off). If the comparison result is less than 0, the output will be conducted in the negative direction and the direction output point is on). When the value is 0, the instruction sets the Done flag to ON. 3. Refer to the DPUDRI instruction for the explanation of other parameters.