AS Series Programming Manual values in the following table. 12. During the weight reading, Status will display corresponding error code and the Error flag changes to ON as an error occurs in the LC module. When the status returns to normal, the Error flag will be cleared automatically. For details on error status, refer to the explanation of status control buffers in the LC module manual. 13. See the sequence diagram of the weight-reading example. En ZeroS TareS TareW Weight _6 Status Explanation of the timing points in the above sequence diagram: Enable the LCWEI instruction.
After getting the command of clearing data to 0, the instruction will clear the values of TareW , Weight and Status . Put the measured stuff on the weighing platform. When the stable weight value is measured, the Status value becomes 1 and Weight displays the weight value. Setting TareS to ON, the Weight value moves to TareW and then the value of Weight is cleared. Setting TareS to Off, the TareW value moves back to Weight and then the TareW value is cleared. Put another measured stuff on the weighing platform.
At the moment, Status enters the status of weight 6-440 Value 0 1 2 3 4 5 Description Weight measuring or no load Weight is stable Hardware fault/ calibration fault In calibration Weight exceeds the range Module number error /channel number error 0 10 0 20 0 10 0 10 20 0 100 0 1 0 1 0 1 0 120