Delta Electronics — 6.19.2 Explanation of Communication Instructions

Chapter 6 Applied Instructions The following table lists the operands for the MODRW instruction. ASCII mode You do not need to convert the ASCII codes, and they are all expressed in 16# values.  AS sends the communication command: “ : 01 06 06 00 55 AA F4 CR LF”  AS receives the communication command: “ : 01 06 06 00 55 AA F4 CR LF” RTU mode  AS sends the communication command: “01 06 06 00 55 AA 36 6D”  AS receives the communication command: “01 06 06 00 55 AA 36 6D” 6_ If the format is correct, SM100 is ON. 4. After receiving the data from the DVP-ES2, the PLC confirms the data format sent back from the DVP-ES2 and determines if it is correct.

If no error occurs in the format, the corresponding special flags SM100 are ON; if not SM102 is ON. 5. When the DVP-ES2 receives this instruction, it writes the data stored in the device D10 to the device T0 in the DVP-ES2. 6. Since this function code writes data, the operand n is ignored. 6-557 Operand Description Device S1 Unit address 1 S2 Function code 16#0006 S3 Device address of T0 16#0600 S Register T0 for reading and writing the data D10 n Data length (not used with this function code) 0