AS Series Programming Manual 5. When X0.0 is ON, the COM1 data exchange table parameters in the AS Series CPU are modified as shown in the following table. 6. Due to the change of COM1 data exchange table parameters, the corresponding data between the AS Series CPU and the DVP-ES2 CPU are modified as shown in the following table. _6 6-602 Item Detection method Remote station Remote Function How to Local device Length No.
address device code start 1 Specified connection 3 D5000 D500 1 H04 Program control D6000 D600 1 H06 2 Specified connection 3 M100 M0 10 H01 Program control M110 M50 10 H0F AS PLC (Master) Content value ES2 PLC (Slave) Content value D5000 3000 D500 3000 D6000 4000 D600 4000 M100-M109 ON M0-M9 ON M110-M119 OFF M50-M59 OFF