AS Series Programming Manual _6 NOTE: the above flags are non-latching types. 6-626 Flag Description Action COM1 COM2 Card 1 Card 2 SM210 SM212 - - Communication mode ON: RTU mode OFF: ASCII mode You can set this value in HWCONFIG in ISPSoft. Not available for Card1 and Card 2. You set the flag to ON and reset it to OFF. SM209 SM211 SM90 SM91 Communication protocol changed flag The communication protocol changes in accordance with the setting values in SR. If the flag is set to ON, the communication protocol changes in accordance with the setting values in SR and then the system automatically resets the flag to OFF. NOTE: this change does not affect the parameters that you set in HWCONFIG.
When the PLC is powered-on again, the PLC operates according to the communication protocol set in HWCONFIG. You set the flag to ON and reset it to OFF.