ASDA-B3 Operation Mode The process of automatically searching for the resonance frequency is shown in the following flowchart. Repeat position control function. 6 No Check if vibration occurs during positioning? Yes Set P1.029 to 1. Decrease the value of P1.030. *1 Increase the value of P1.030. *2 Yes No Yes Vibration reduced? Check if P1.029 No is set to 0? Check if P1.026 and P1.028 are set to 0? No Yes Set P1.029 to 0. Operation complete Note: 1. When the values of P1.026 and P1.028 are both 0, it means the frequency cannot be found. It is probably because the detection level is set too high causing the low-frequency vibration not being able to be detected. 2.
When the value of P1.026 or P1.028 is greater than 0, but the vibration cannot be suppressed, it is probably because the detection level is too low causing the system to detect minor frequency or noise as low-frequency vibration. 3. When the auto suppression procedure is complete, but the vibration persists, you can manually set P1.025 or P1.027 to suppress the vibration if you have identified the low frequency. 6-13