Delta Electronics — 6.6.3 Analog monitoring

ASDA-B3 Operation Mode 6.6.3 Analog monitoring You can find the required voltage signal with analog monitoring. The servo drive provides two analog channels. Refer to Chapter 3 for more information about wiring. 6 Refer to Chapter 8 for detailed descriptions of the relevant parameters. P0.003 Analog output monitoring P1.003 Encoder pulse output polarity P1.004 MON1 analog monitor output proportion P1.005 MON2 analog monitor output proportion P4.020 Offset adjustment for analog monitor output (Ch1) P4.021 Offset adjustment for analog monitor output (Ch2) Example: Specify a motor speed of 1,000 rpm, which corresponds to analog voltage output of 8V with the maximum speed of 5,000 rpm.

The setting is as follows: P1.004 = Required speed Max. speed x 100% = 1000 rpm 5000 rpm Ч 100% = 20% You can calculate the corresponding voltage output for the current motor speed with the following formula. 6-35 Parameter Function Motor speed MON1 analog monitor output 300 rpm Current speed 300 rpm MON1 = 8V × ×100% = 8V × ×100% = 2.4V Max. speed × P1.004 5000 rpm × 20 100 100 900 rpm Current speed 900 rpm MON1 = 8V × ×100% = 8V × ×100% = 7.2V Max. speed × P1.004 5000 rpm × 20 100 100