MODBUS Communication ASDA-B3 9.4 Writing and reading communication parameters Refer to Chapter 8 for the descriptions of the parameters that you can write or read through the 9 communication interface. The ASDA-B3 servo drive parameters are divided into eight groups: Group 0 (Monitoring parameters), Group 1 (Basic parameters), Group 2 (Extension parameters), Group 3 (Communication parameters), Group 4 (Diagnosis parameters), Group 5 (Motion control parameters), and Group 6 and Group 7 (PR parameters). Writing parameters through communication You can set these parameters through communication: Group 0, except P0.000 - P0.001, P0.008 - P0.013, and P0.046.
Group 1 Group 2 Group 3 Group 4, except P4.000 - P4.004 and P4.008 - P4.009. Group 5, except P5.010, P5.016, and P5.076. Group 6 Group 7 Note the following additional details: P3.001: when changing the communication speed, the next data is written at the new transmission speed after the new speed is set. P3.002: when changing the communication protocol setting, the next data is written with the new communication protocol setting after the new values are set. P4.005: JOG control. Refer to Chapter 8 for detailed descriptions. P4.006: force digital output (DO) contact control. You can use this parameter to test the DO contacts.
Set P4.006 to 1, 2, 4, 8, 16, and 32 to test DO1, DO2, DO3, DO4, DO5, and DO6, respectively. Then, set P4.006 to 0 to complete the test. P4.010: adjustment function. First set P2.008 to 20 (14H in hexadecimal format) to enable this function. P4.011 - P4.021: these parameters are for adjusting the hardware offset. The parameters were adjusted before delivery, so changing the parameter settings is not recommended. If you need to modify these parameters, first set P2.008 to 22 (16H in hexadecimal format). Reading parameters through communication You can read the values from all parameters of Group 0 to Group 7 through communication. 9-14