TROUBLESHOOTING C-5 C-5 [E203] Short circuit in swing holding brake solenoid system is displayed # This troubleshooting is carried out when there is still an abnormality, so when disconnecting the connector and inserting the T-adapter, or when removing the T-adapter and returning the connector to its original position, if an E service code is not displayed, the problem has been removed. # If the starting switch is turned OFF after an abnormality occurs, turn the starting switch ON and check if an E service code is displayed. (If it is not displayed, the problem had been removed). # Always turn the swing lock prolix switch OFF, then turn the swing lock switch OFF before checking.
# Before carrying out troubleshooting, check that all related connectors are properly inserted. # Always connect any disconnected connectors before going on the next step. Note: When the swing prolix switch is operated, error [E203] is detected, but this is not a failure. Note: If error [E203] is generated when the swing lock is operated, carry out troubleshooting F-9 for failure in the swing lock signal input system. Table 1 20-178 Troubleshooting No. 3 Voltage Measurement conditions Between A26 (1) - chassis 0 - 10 V 4 - 5 sec after all levers placed at neutral 20 -30 V Swing or work equipment lever operated slightly (not enough to move swing or work equipment)