Komatsu — 4.10.3 GENERATOR - CHECK BELT TENSION

MAINTENANCE 4.10 EVERY 250 OPERATING HOURS OR MONTHLY 4.10.3 GENERATOR - CHECK BELT TENSION REMARK For the correct belt tension and belt tension gauge refer to the Drive Belt Tension Chart in the Engine Operation and Mainte- nance Manual, Section V, page 19. The engine can be equipped with one of the two versions of belt tensioning systems. Version A with turn buckle, illust. Z 25103 Adjustment: 1. Remove generator belt guard. 2. Loosen bolts (1 and 2). 3. Loosen lock nuts (3) and adjust belt tension with turn buckle (4). 4. Tighten lock nuts (3) and bolts (2 and 1) in this sequence. 5. Install generator belt guard. Version B with slotted bar, illust. Z 25103 Adjustment: 1.

Remove generator belt guard. 2. Loosen bolts (1 and 2). 3. Pull the generator until the required belt tension is obtained and tighten bolts (2 and 1) in this sequence. 4. Install generator belt guard. NOTICE Check the belt tension after 10 minutes running time and readjust if necessary. 321