EPA07 SERIES 60 ENGINE OPERATOR'S MANUAL Item 5 – Turbocharger, Air-to-Air Charge Cooler is factory-calibrated and is not adjustable. Check actuator operation at the intervals shown in the maintenance schedule. Visually inspect the turbocharger mountings, intake and exhaust ducting and connections for leaks daily. EYE INJURY PERSONAL INJURY To avoid injury from flying debris when using compressed air, wear adequate eye protection (face shield or safety goggles) and do not exceed 276 kPa (40 psi) air pressure. To avoid injury from hot surfaces, wear protective gloves, or allow engine to cool before removing any component.
Check the lube oil inlet and outlet lines for leaks or restrictions to oil flow. Check for unusual noise or vibration and, if excessive, stop the engine and do not operate until the cause is determined. Item 6 Battery Check the hydrometer of maintenance-free batteries for charge. See Figure 23. Periodically inspect the air-to-air charge cooler (if used) for buildup of dirt, mud, etc. and wash off. Check the charge cooler, ductwork, and flexible connections for leaks and have repaired or replaced, as required. Check turbocharger heat-insulating exhaust system blankets (if used) for damage on a daily basis.
Torn, matted, crushed, oil-soaked or otherwise damaged insulation blankets must be replaced immediately. Figure 23 Maintenance-Free Battery Wastegated Turbochargers The turbocharger wastegate actuator All information subject to change without notice. 79 DDC-SVC-MAN-0006 Copyright © 2009 DETROIT DIESEL CORPORATION