heidenhain PWT 100, PWT 101 — 8.6.7 Encoder status screen for TTL/HTL/HTLs

8 Encoder diagnostics | Diagnosis for encoders with TTL/HTL/HTLs/ interface 8.6.7 Encoder status screen for TTL/HTL/HTLs Figure 52: Encoder status screen (TTL) The Encoder status screen displays encoder errors. The Encoder status screen can be opened from the following screens, using the Status button: PWT display screen Counts screen Switching signals screen Level display screen Classification of status messages The messages displayed by the product for the TTL interface are classified as follows:

Status screen Message Description Red Amplitude error Signal amplitude is too small ( PP or 3 µA PP ) or too large (> 1.35 V PP or 18 µA PP ) Red Counting error A counting error occurred (counting order Ua1, Ua2 is incorrect or the counting interval is too small) Red Fault-detec- tion signal For more information, please refer to the documen- tation about the encoder or the "Interfaces of HEIDENHAIN Encoders" brochure. Red Invalid numeri- cal value between two reference marks An incorrect count value was detected while checking the position during reference-mark crossover. Example:

When using a rotational encoder with a reference mark, a distance of 0 or the line count must always be detected between two reference marks. Red Reference mark not found A reference mark that was expected due to the current position value could not be identified. Example: When using a rotational encoder with a reference mark, a reference mark must always be identified at position 0 after referencing. HEIDENHAIN | PWT 100, PWT 101 | Operating Instructions | 07/2024 115