Section C - Electrics Basic System Operation Hydraulic Temperature Sensor/Warning Hydraulic Temperature Sensor/Warning Operation C005700GB-2 Fig 80. The hydraulic system is fitted with a thermistor and a thermal switch to measure temperatures. The temperature is displayed to the operator by means of a bar graph gauge. The actual values can be displayed via the EMS's SET and MODE menu. When the hydraulic oil temperature reaches 97єC the EMS will illuminate the warning lamp. If the temperature continues to rise the bar graph will flash on-off and an audible warning and "HYD.TEMP" message will be given. The audible warning can be cancelled by pressing the "ACK" button on the EMS.
The overheat switch is included as a safety measure in case of the thermistor failure. If this input is grounded then the EMS will illuminate the warning lamp, sound the audible alarm and display the overheat message. The audible warning can be cancelled by pressing the "ACK" button on the EMS. Note: When the temperature reaches 98°C the pump should be lowered to E mode. C-87 C-87 9803/9880-3