JCB — 80.pdf (p.80)

Section B - Body and Framework Technical Data Air Conditioning (option) Air Conditioning (option) Automatic Temperature Control (ATC) System TB-012 Table 3. Table 4. Table 5. B-5 B-5 9803/9880-3 Pressure Switch Setting Bar lbf/in2 Low Pressure Cut In 1.4 (+/- 0.1) 20 (+/- 1.5) Low Pressure Cut Out 0.3 (+/- 0.1) 4 (+/- 1.5) High Pressure Cut In 17.2 (+/- 0.7) 250 (+/- 10) High Pressure Cut Out 27.6 (+/- 0.7) 400 (+/- 10) Refrigerant Gas Charge Weight R-134a 1400g +/- 10g Oil Quantity Full System 150g +/- 5g PAG (PolyAlkylene Gycol) oil to ISO 100 Evacuation/Charge If the system is being evacuated, add 57g (59ml) of lubrication oil to the system before or during the charge.