N38143 Chapter 6 Controller wiring table System wiring Resistance in the wiring, due to inadequate wire gauge or excessive wire length, will result in insufficient force from the actuator.The table shows the recommended gauges and maximum lengths of wires. Wire length is the total length used to connect the actuator to the controller and controller to the system power. Page 47 Model 3100 Battery Red + Black - Actuator White + White/Black - Speed signal input Magnetic pickup Blue + Green - 1500 (50Hz) Violet 1800 (60Hz) Gray Service tool Yellow Tx Orange Rx System wiring table AWG14 (2.50mm2) AWG16 (1.50mm2) AWG18 (1.00mm2) 66ft (20m) 33ft (10m) 22ft (6.7m)