OM2049 2/13 Safety - Section 20 Page 20-19 FIGURE 20-10. CAPACITOR TERMINAL POLARITY MANUAL DISCHARGE OF CAPACITORS 3. Discharge the relevant capacitors. Open the door(s) and place one grounding stick on one of the positive (+) capacitor terminals and the other on the diagonally located negative (-) terminal. Refer to Figure 20-10 and Figure 20-12. Attempt to minimize the time between application of the positive stick and the negative stick so that the current flow will be positive to negative rather than either to ground. Leave sticks in place until capacitors are discharged. Refer to Figure 20- 12.
If the voltage is greater than 1V on any of the capaci- tors, the capacitor must be manually discharged. With a suitable capacitor discharge device, such as ground stick pair (PC3299), discharge the capacitors where needed per the following instructions: 1. With the control cabinet high voltage compart- ment doors closed, connect the ground stick pair ground lead to ground. The most convenient location is the middle top bolt that attaches the door center post to the control cabinet frame. 2. Verify the ground connection and ground stick resistance levels.
Measure the resistance between each individual ground stick tip to either the GND1 or GND2 ground block in the low volt- age compartment of the control cabinet using a multimeter (Figure 20-11). Ensure that the resis- tance is within the manufacturer’s specifications for the ground sticks. NOTE: On the capacitors located behind the door post, it is difficult to access diagonal terminals on the same capacitor. If using adjacent terminals, use care to keep the tips separated while discharging or else use a positive terminal on one capacitor and negative terminal of the adjacent capacitor on the same bus bar. For PC3299 grounding sticks, the discharge times from 2000 volts are:
For PC3299 grounding sticks, the valid range is 80 to 125 ohms per stick. 15 seconds (maximum) for 2 capacitors 75 seconds (maximum) for 10 capacitors Hazardous voltages are present in this equipment. Avoid touching any energized equipment when the door to the low voltage area is open. Failure to do so may result in personal injury and equipment damage.