DISTRIBUTION SYSTEMS - SECONDARY HYDRAULIC POWER SYSTEM Sensing system Differential pressure switch - Short circuit to B+ (A.12.A.95.81 - G.30.B.54) AFX8010 E0007-03 - PTO Filter Restriction Switch Cause: The PTO box filter bypass switch (S34) circuit is shorted to a higher than normal voltage source. Possible failure modes: 1. Sensor supply wiring shorted to 12 volts . 2. Controller internal failure (internal regulator failure). Solution: 1. Enter the Universal Display Plus "DIAG" screen. Select the "HYDRAULIC" sort menu, and select "PTO FILTER SW" to check the voltage range. The normal operating range for the PTO box filter bypass is 1.8 - 10.0 volts A.
If the voltage reading is 10.0 volts or greater, continue with Step 2 . B. If the voltage reading is within the proper limits, the shorted wire may not be powered up at this time. Continue the troubleshooting at Step 4 . 2. Disconnect the PTO box filter bypass pressure switch connector X238 . A. If the voltage drops below 10.0 volts , the short is in the sensor, or sensor wiring. Replace the sensor. B. If the voltage is above 10.0 volts , continue with Step 3 . 3. Disconnect the straw hood front (SW) harness from the main frame (MF) harness at connector X024 . A.
If the voltage drops below 10.0 volts , the short is in the straw hood front (SW) harness between connector X024 and connector X238 wire 448 yellow. Locate the short and repair. B. If the voltage remains above 10.0 volts , the short is in the main frame (MF) harness between connector X024 and connector X019 pin J2-35 wire 448 yellow. Locate the short and repair. 4. Visually inspect the harness and connectors for damage, bent or dislocated pins, corroded terminals or broken wires. A. If no damage is found, erase the fault code and continue operation. 9666 1 27/05/2004 A.12.A / 3