Case IH AFX8010 — TILTING

TOOL POSITIONING - TILTING Control valve Lateral tilt valve - Short circuit to ground (G.20.A.13.20 - G.30.B.53) AFX8010 E0048-04 - Header Tilt Current Sense Context: The Header Tilt Current Sense circuit is the ground path for the header tilt CW and header tilt CCW PWM solenoids. By monitoring current flow on the return path of the solenoids, the module can provide precise control of solenoid engagement. When this error message is reported, this is an indication that the output is engaged, but the sense line does not detect any current flow - the circuit is grounded externally from the module. Cause:

The header tilt CW (L-18) or header tilt CCW (L-19) circuits are grounded at an external point. Possible failure modes: 1. Bad solenoid. 2. Return side wiring shorted to ground. 3. Controller internal failure (internal regulator failure). Solution: 1. Enter the Universal Display Plus "DIAG" screen. Select the "HDR HEIGHT/TILT" sort menu, and select "TILT CCW VLV" or "TILT CW VLV" to monitor the current flow. Use the "COMMAND" and "ENGAGE" functions to power the circuit at 100% output. Test both header tilt CW and tilt CCW circuits. The proper current for both header tilt CW and header tilt CCW should be approximately 1.0 - 1.5 amps . A.

If there is no current reading on either circuit, the circuit is grounded externally from the module. Continue with Step 2 . B. If the readings are normal ( 1.0 - 1.5 amps ), continue the troubleshooting at Step 4 . NOTE: If the current reading is high, immediately shut off the circuit after verifying the reading to prevent module damage. 2. Turn the key switch to the OFF position and disconnect the feeder valves connector X021 . Use a multimeter to check for continuity between the header tilt CW solenoid L-18 connector X021 pins G or H and chassis ground. Repeat this continuity check between the header tilt CCW solenoid L-19 connector X021 pins J or K and chassis ground.

There should not be continuity to ground. A. If there is continuity to ground on either solenoid, replace the solenoid. B. If there is no continuity to ground on either solenoid, continue with Step 3 . 3. Carefully disconnect connector X019 on the bottom of CCM1 module. Use a multimeter to check for continuity between the harness end of connector X021 pin H and chassis ground. Repeat this continuity check between the harness end of connector X021 pin K and chassis ground. There should not be continuity to ground. A. If there is continuity to ground, continue with step 4 . B. If there is no continuity to ground, continue with Step 4 . 4. Disconnect connector X008 .

Use a multimeter to check for continuity between connector X008 pin 13 and chassis ground. There should not be continuity to ground. A. If there is no continuity to ground, there is a short to ground in the front frame (FF) harness between connector X021 and connector X008 wires 553 blue, 554 blue or 555 blue. Locate the short and repair. B. If there is continuity to ground, there is a short to ground in the main frame (MF) harness between connector X008 and connector X019 pin J2-10 wire 555 blue. Locate the short and repair. 9707 1 27/05/2004 G.20.A / 10