CROP PROCESSING - RESIDUE HANDLING Spreader Sensing system Speed sensor - Short circuit to B+ (K.64.D.95.80 - G.30.B.54) AFX8010 E0144-03 - Spreader Speed Sensor Cause: The spreader RPM sensor (B-55) circuit is shorted to a higher than normal voltage source. Possible failure modes: 1. Sensor supply wiring shorted to 12 volts . 2. Controller internal failure (internal regulator failure). Solution: 1. Enter the Universal Display Plus "DIAG" screen. Select the "RESIDUE" sort menu, and select "SPREADER SPD SE" to check the voltage range.
The proper voltage for sensor when blocked by ferrous metal - 5.6 - 7.3 volts The proper voltage for sensor when not blocked by ferrous metal - 0.5 - 5.6 volts The proper voltage sensor when disconnected - 7.3 - 9.0 volts . A. If the voltage reading is high out of range 9.0 - 10.0 volts , continue with Step 2 . B. If the voltage reading is within the proper limits, the shorted wire may not be powered up at this time. Continue the troubleshooting at Step 6 . NOTE: Visually inspect the wiring harness and connectors. Verify that the connector was fully installed. Inspect the terminals and wires at the connector for pushed back or corroded terminals or damaged wires.
Flex the harnesses involved to reveal intermittent breaks or shorts in the wiring concerned. 2. Disconnect the spreader RPM sensor connector X383 . A. If the voltage drops to 7.3 - 9.0 volts , the short is in the sensor, or sensor wiring. Replace the sensor. B. If the voltage remains high, continue with Step 3 . 3. Disconnect the straw hood rear (SH) harness and straw hood front (SW) harness at connector X071 . A. If the voltage drops to 7.3 - 9.0 volts , the short is in the straw hood (SH) harness between connector X071 and connector X383 wire 414 yellow. Locate the short and repair. B. If the voltage remains high, continue with Step 4 . 4.
Disconnect the straw hood front (SW) harness and main frame (MF) harness at connector X024 . A. If the voltage drops to 7.3 - 9.0 volts , the short is in the straw hood front (SW) harness between connector X071 and connector X024 wire 414 yellow. Locate the short and repair. B. If the voltage drops to 7.3 - 9.0 volts , the short is in the main frame (MF) harness between connector X024 and connector X016 wire 414 yellow. Locate the short and repair. 5. Visually inspect the harness and connectors for damage, bent or dislocated pins, corroded terminals or broken wires. A. If no damage is found, erase the fault code and continue operation. 9721 1 27/05/2004 K.64.D / 19