Perkins — 1106DO&M2ACOVERTOP43.pdf

SEBU8 119-01 14 Safety Section Engine Stopping (02294873 Grounding Practices Engine Stopping Stop the engine according to the procedure in the Operation and Maintenance Manual, “Engine Stopping (Operation Section)” in order to avoid overheating of the engine and accelerated wear of the engine components. Use the Emergency Stop Button (if equipped) ONLY in an emergency situation. Do not use the Emergency Stop Button for normal engine stopping. After an emergency stop, DO NOT start the engine until the problem that caused the emergency stop has been corrected. Stop the engine if an overspeed condition occurs during the initial start-up of a new engine or an engine that has been overhauled.

To stop an electronically controlled engine, cut the flustration 12 power to the engine and/or shutting off the air supply Typical example to the engine. (1) Starting motor to engine block (2) Ground to starting motor (3) Ground to battery g01162916 02234878 Electrical System Never disconnect any charging unit circuit or battery circuit cable from the battery when the charging unit is operating. A spark can cause the combustible gases that are produced by some batteries to ignite.

To help prevent sparks from igniting combustible gases that are produced by some batteries, the negative “~" cable should be connected last from the axternal power source to the negative “~” terminal of the starting motor. If the starting motor is not equipped with a negative ‘-” terminal, connect the cable to the engine block. Check the electrical wires daily for wires that are loose or frayed, Tighten all loose electrical connections before the engine is started. Repair all frayed electrical wires before the engine is started. \ Wustration 13 See the Operation and Maintenance Manual for Typical example specific starting Instructions.

(4) Ground to engine (5) Ground to battery gO1162918 Correct grounding for the engine electrical system is necessary for optimum engine performance and reliability. Incorrect grounding will result in uncontrolled electrical circuit paths and in unreliable electrical circuit paths.