SYSTEM / Control System Hydraulic Fan Cooling Control Purpose: Improving fuel consumption rate and noise reduction by restricting the hydraulic fan speed in response to oil temperature and coolant temperature. Operation: 1. When the engine is started, the fan pump rotates, and discharges oil to the fan motor. 2. Signals from the hydraulic oil temperature sensor, engine coolant temperature sensor, and torque converter oil temperature sensor are simultane- ously transmitted to the MC, and arithmetic op- eration of three target hydraulic fan speeds are carried out. 3. MC selects the highest speed, and transmits sig- nal to the flow control solenoid valve. 4.
Flow control solenoid valve operates, and pres- sure oil coming from it flows into the right end of the flow control valve, so the flow control valve spool moves left. 5. When the flow control valve spool moves left, part of the pressure oil flowing to the fan motor flows to the tank port, and the fan motor speed is lowered accordingly. 6. In case oil temperature or coolant temperature of any part is above the set temperature, the hy- draulic fan speed is maximum when the engine speed is maximum. 7. In case oil temperature or coolant temperature of any part is below the set temperature, the hydrau- lic fan speed is lowered in response to the datum of the highest temperature. 8.
Besides, the signal from the outside air tempera- ture sensor also enters the MC, and rotates the fan always at the maximum speed, disregarding the controls in 2 through 7 in case the air condi- tioner switch is ON at the outside air temperature of 35 ° C (95 ° F) and above. NOTE: In case any of the engine speed sensor, hydraulic oil temperature sensor, engine coolant temperature sensor, torque con- verter oil temperature sensor and out side temperature sensor becomes out of order, cooling by hydraulic fan control is always made at the maximum speed. T2-1-42