TROUBLESHOOTING / Troubleshooting B Relation between Refrigerant Quantity and Refrigerant Flow in Sight Glass: W115-02-10-019 Bubbles exist: Bubbles are seen in refrigerant flow as both liquid refrigerant and refrigerant gas exist, being mixed. W115-02-10-020 Transparent: Refrigerant flow is transparent as only liquid refrigerant exists. 115-02-10-021 Milk white: Refrigerant flow shows thin milk white as oil and refrigerant are separated. CAUTION: Wait until the high-pressure-side pressure drops to less than 980 kPa (10 kgf/cm 2 , 142 psi) before attempting to dis- connect the high-pressure-side charge hose. Otherwise, refrigerant and compressor oil may spout. 13.

After checking refrigerant quantity, disconnect the low-pressure-side charge hose first. Wait for the high-pressure-side pressure to drop to less than 980 kPa (10 kgf/cm 2 , 142 psi). Disconnect the high-pressure-side charge hose. T5-6-105 Refrigerant Quantity Refrigerant Flow in Sight Glass (approx. 1 min. after air conditioner switch is turned ON) Explanation for Refrigerant Flow in Sight Glass Adequate (immediately after) (approx. 1 mm after) W115-02-10-016 Immediately after the air conditioner is turned ON, few bubbles are seen. Then the flow becomes transparent and shows thin milk white color. Overcharged W115-02-10-017 No bubbles are seen after the air conditioner is turned ON.

Not Enough W115-02-10-018 Bubbles are seen continuously after the air condi- tioner is turned ON.