Cummins — Cummins CFP83 Series Fire Pump Drive Engines Operation & Maintenance Manual

Section 6 – System Diagrams Page 6-13 CFP83 Series Assembly Diagram, Raw Water Piping Raw water is used to cool the engine coolant and is supplied from the fire pump prior to the pump discharge flange. It is forced through a cooling loop by fire pump pressure to the engine heat exchanger. Then it is discharged to an open waste cone. The following raw water manifold is available as an option (Cummins NPower Part No. 9659). If supplied by the customer, National Fire Protection Association (NFPA) Pamphlet No. 20 lists the components that are required. Refer to the Cooling System Specifications in Section 10 for process requirements.

Refer to Raw Water Piping, Lineup, and Configuration in Section 3. 1 2 3 4 12 5 11 7 10 6 9 8 1. Supply Pressure Gauge 7. Bypass Inlet Valve 2. Supply Pressure Gauge Isolation Valve 8. Normal Inlet Valve 3. 1” supply to the heat exchanger 9. Normal Strainer 4. Bypass Outlet Valve 10. Normal Pressure Regulator 5. Bypass Pressure Regulator 11. Solenoid Operated Valve 6. Bypass Strainer 12. Normal Outlet Valve Drawing No. 9777, Section 6, Rev. 02-07