Cummins — Cummins CFP83 Series Fire Pump Drive Engines Operation & Maintenance Manual

Section 7 – Adjustment, Repair, and Replacement Page 7-135 CFP83 Series Measure Fuel Inlet Restriction Prepare Measure Install a fitting at the transfer pump fuel inlet Install a vacuum gauge that has a range of at least 0 to 508 mm Hg [0 to 20 in Hg]. Start the engine, and run at low or high idle. Maximum Allowable Inlet Restriction at Low/High Idle: 101.6 mm-hg [4.0 in-hg] Drawing No. 9777, Section 7, Rev. 02-07