Cummins — Cummins CFP83 Series Fire Pump Drive Engines Operation & Maintenance Manual

Section 12 – Troubleshooting Page 12-71 CFP83 Series Engine Will Not Shut Off Remotely NOTE : Stop the engine mechanically by moving the manual shutoff lever to the STOP position. Refer to Emergency Manual Stopping Procedure in Section 3. Drawing No. 9777, Section 12, Rev. 02-07 Cause Correction Stop circuit malfunction in the fire pump controller of field wiring. NOTE: In the AUTO mode, the fire pump engine stops upon loss of signal power from the fire pump controller. Check the engine stop circuit in the fire pump controller. Correct any faults. Check for short to voltage on the signal wiring from the fire pump controller to the engine control panel. Correct any faults.

Check operation of the switch contacts of the AUTO/MANUAL switch at the engine control panel. Replace the switch if the switch contacts fail to operate properly. Fuel shutoff valve (FSOV) is malfunctioning. Check for correct solenoid operation. Refer to Fuel Shutoff Valve (005-043) in Troubleshooting and Repair Manual C Series Engines, Bulletin Number 3666003-02. Engine is running on fumes drawn into the air intake. Check the air intake ducts. Locate and isolate the source of the fumes. Repair as necessary. Fuel injection pump is malfunctioning. Replace the fuel pump.

Refer to Fuel Injection Pumps, In-Line (005-012) in Troubleshooting and Repair Manual C Series Engines, Bulletin Number 3666003-02. Contact an Authorized Cummins Repair Facility.