Cummins — Cummins CFP83 Series Fire Pump Drive Engines Operation & Maintenance Manual

Page 3-64 Section 3 – Installation and Operation CFP83 Series Starting Procedure - After Extended Shutdown or Oil Change Complete the following steps after each oil change, or after the engine has been shut off for more than 30 days to make sure the engine receives the correct oil flow through the lubricating oil system: Bump the engine. Refer to Pre-Lubricate the Engine in this section. Depending upon the nature of the shutdown, perform other installation checks in this section as appropriate. Start the engine. Refer to Normal Local Starting Procedure in this section. If required, vent the fuel system. Refer to Air in Fuel in Section 7. Drawing No. 9777, Section 3, Rev. 02-07