Section 50 - Climate Control - Chapter 1 ATC Fault Code 133 Low pressure switch (-) shorted to ground Cause: Wire harness/connector failure NOTE: If system is properly charged, then the low pressure switch will be closed and the short could be on either leg of the switch. ATC module failure Possible failure modes: Compressor clutch disabled. Solution: 1) Inspect harness and connectors for possible shorting between low pressure switch wires (both leads) and other wires. If a short exists, then replace harness. 2) If no fault found with wire harness or connectors, then replace ATC module. ATC Fault Code 134 Low pressure switch open for more than 1 minute Cause:
Incorrect charge in system Wire harness/connector failure NOTE: If system is properly charged, then the low pressure switch will be closed and the failure could be on either leg of the switch. Low pressure switch failure ATC module failure Possible failure modes: Compressor clutch locked out until unit is cycled off then back on. Solution: 1) Verify that system charge is within specification. 2) Disconnect low pressure switch from harness and check its resistance. It should be closed (measure around 0 Ohms) if system charged correctly. Replace if faulty.
3) Inspect harness and connectors for possible shorting between low pressure switch wires (both leads) and other wires or possible open condition. If a short or open exists, then replace harness. 4) If no fault found with system charge, wire harness, connectors, or low pressure switch, then replace ATC module. 50-1-26