TwinFlow Fire Pump 90.00 Troubleshooting 3. Using the pump’s priming devices, develop a vacuum of at least 22 inHg (74.5 kPa) for 30 seconds for pumps up to 1250 gpm, or 45 sec- onds for pumps 1500 gpm or greater. 4. Reduce the maximum vacuum attained by 1 inHg (3.4 kPa) for each 1000 ft. (305 m) of el- evation of the test site above 2000 ft (610 m). NOTE: The vacuum should not drop more than 10 inHg (33.9 kPa) in 5 minutes. Do not operate the pump priming device once the five-minute test has begun. Business Class M2 Workshop Manual, Supplement 8, September 2005 300/6