Caterpillar — MAINTENANCE INTERVAL SCHEDULE (STANDBY GENERATOR SET ENGINES)

105 Maintenance Section Cooling System Coolant Analysis (Level Il) - Obtain For information regarding the disposal and the recycling of used coolant, consult your Caterpillar dealer or consult Caterpillar Service Technology Group: Outside U.S.A.: (309) 675-6277 Inside U.S.A.: 1-800-542-TOOL Inside Illinois: 1-800-541-TOOL Canada: 1-800-523-TOOL CSTG COSA Geneva, Switzerland: 41-22-849 40 56 Clean the Cooling System 1. After the cooling system has been drained, flush the cooling system with clean water in order to remove any debris. 2. Close the coolant drain. Clean the drain plugs and install the drain plugs. NOTICE Fill the cooling system no faster than 19 L (5 US gal) 2.

Open the water inlet for the separate circuit aftercooler (if equipped). Start the engine. Operate the engine in order to purge the air from the cavities of the engine block. Allow the ELC to warm and allow the coolant level to stabilize. Stop the engine. 3. Check the coolant level. Maintain the coolant to the proper level on the sight gauge (if equipped). If a sight gauge is not equipped, maintain the coolant within 13 mm (.5 inch) below the bottom of the filler pipe. 4. Clean the radiator filler cap. Inspect the gaskets of the radiator cap. If the gaskets of the radiator filler cap are damaged, discard the old radiator filler cap and install a new radiator filler cap.

If the gaskets of the radiator filler cap are not damaged, use a 9S-8140 Pressurizing Pump in order to pressure test the radiator filler cap. The correct pressure is stamped on the face of the radiator filler cap. If the radiator filler cap does not maintain the correct pressure, install a new radiator fifler cap. per minute to avoid air locks. 5. Start the engine. Inspect the cooling system for 3. Open the water inlet for the separate circuit aftercooler (if equipped). Fill the cooling system with clean water. Install the radiator filler cap. Operate the engine until the temperature reaches 49 °C (120 °F) to 66 °C (150 °F). 4. Stop the engine and allow the engine to cool.

Close the water inlet for the separate circuit aftercooler (if equipped). Ensure that the engine will not start when the cooling system is drained. Loosen the radiator filler cap slowly in order to relieve any pressure. Remove the radiator filler cap. 5. Open Cooling System Coolant Analysis (Level Il) - Obtain SMCS Code: 1350 For conventional heavy-duty coolant/antifreeze, check the concentration of supplemental coolant additive (SCA) regularly. The concentration of SCA can be checked with an S-O-S coolant analysis the coolant drain. Remove the drain plugs. Allow the coolant to drain. Flush the cooling system with clean water. Close the coolant drain. Install the drain plugs. 6.

Repeat leaks and for proper operating temperature. Steps 3, 4, and 5. Fill the Cooling System NOTICE Fill the cooling system no faster than 19 L (5 US gal) per minute to avoid air locks. 1. Fill the cooling system with Extended Life Coolant (ELC). After filling the cooling system, do not install the radiator filler cap. (Level |). A more detailed coolant analysis is recommended periodically. For example, considerable deposits are found in the water jacket areas on the external cooling system, but the concentrations of coolant additives were carefully maintained. The coolant water probably contained minerals which were deposited on the engine over time.

A coolant analysis can be conducted in order to verify the condition of the water that is being used in the cooling system. A full water analysis may be obtained from the following sources: e Caterpillar dealer e Local water utility company e Agricultural agent e Independent laboratory