Batteries C Series Page 13-4 Section 13 - Electrical Equipment - Group 13 Batteries (013-007) Inspect Use an inductive charging and cranking system analyzer to load-test the state of charge of maintenance-free batteries. If the state of charge is low, use a battery charger to charge the battery. Refer to the manufacturer's instructions. Replace the battery if it will not charge to the manufacturer's specifications or the battery will not maintain a charge. If conventional batteries are used, remove the cell caps or covers and check the electrolyte (water and sulfuric acid solution) level. WARNING Batteries can emit explosive gas.

To reduce the possibility of personal injury, always ventilate the compartment before servicing the batteries. To reduce the possibility of arcing, remove the battery (-) negative cable first and attach the battery negative cable last. NOTE: Maintenance-free batteries are sealed and do not require the addition of water. Fill each battery cell with water. Refer to the manufacturer's specifications. Refer to the accompanying table to determine the battery state of charge based on the specific-gravity readings. Use a hydrometer to measure the specific gravity of each cell. NOTE: If the specific gravity of any cell is below 1.200, the battery must be charged. NOTE:

Do not attempt to check the specific gravity of a battery immediately after adding water. If it is necessary to add water to allow use of the hydrometer, charge the battery several minutes at a high rate to mix the electrolyte. Battery State of Charge Specific Gravity @ 27°C [80°F] 100% 1.260 to 1.280 75% 1.230 to 1.250 50% 1.200 to 1.220 25% 1.170 to 1.190 Discharged 1.110 to 1.130