Cummins — 3666003

Generator, Main C Series Page 21-4 Section 21 - Main Power Generator - Group 21 1. Digital display 2. LED indicator lights 3. Button A: Toggles between instrument view and 6. Backlight on/off 7. Alarm acknowledge 8. Start button 9. Stop button. alarm list view 4. Button B: Toggles between two instrument views 5. Alarm silence The classed base panel has built in alarms. See Table 2. Operation of the Classed Base Panel - The classed base panel has several different screens or views. The views include two instrument views, alarm list view, information view, and event log view. To toggle between instrument view and alarm list view, press button A (See Figure 2).

To toggle between two instrument views, press button B (See Figure 2). To go to information view, press and hold button A for approximately one second. To go to event log view, press and hold button B for approximately one second. When connected to the classed remote panel, both the classed remote panel and the classed base panel can control the engine. However, it is possible to lock out the classed remote panel and allow control only from the classed base panel. To lock out the classed remote panel: 1. Go to INFO view 2. Press and hold BUZZER ON/OFF for two seconds until a beep is heard. The screen will change to toggle Local Mode ON/OFF. When ON, this disables the remote panel commands.

Stop Button - To stop the unit, press and hold the red button labeled STOP until the unit has stopped. If the Stop Button is held for less than one half of a second, the engine will not stop. The control unit stops the generator set by pulling the stop solenoid. When the red LED in the stop button is lit it indicates that the control unit is pulling the stop solenoid. Start Button - Manual start is activated with the green button labeled Start. Press and hold the button until the engine has started. A running engine is indicated by the green LED in the Start button and the text Running in the far left status field on the Digital Display. The RPM-meter will indicate the engine speed.

Standby and Manual Mode Button - The Standby button is a toggle button, meaning that for every other keypress, the unit is set to Standby or Manual. A green LED in the Standby button indicates that the unit is set to Standby. The right most status field also indicates the chosen mode by displaying either Standby or Manual. Acknowledge (Reset) Button - In case of alarms, a press on the acknowledge button, labeled Ackn, will reset the alarm(s). At the same time, the buzzer will be silenced. In the Alarm List view, Ackn will reset all alarms, whereas, in the Instrument view, Ackn will reset the alarm in the top of the screen only .

Buzzer OFF Button - Press the Buzzer OFF button to silence the built-in buzzer signal that is activated when an alarm occurs. The alarm that activated the buzzer remains active until acknowledged. Classed Remote Panel Digital Display - The classed remote panel is a touch screen display that shows most of the data available from the classed base panel. It can also execute many of the same commands as the base panels. It connects to the supplied terminals on the engine cabinet with six wires. Four wires are for communication and two are for power supply. See Figure 3 for the Classed Remote Panel Digital Display. Table 2: Classed Base Panel Built in Alarms.

Alarm Description Low Battery Voltage Low voltage at the start battery Secondary Battery Low Voltage Low voltage at the secondary battery source Overspeed Engine running faster than the overspeed set-point Engine Stopped Engine stopped for no known reason Engine Failed to Stop 60 seconds after issuing the stop command, the engine has still not stopped Start Failure Engine failed to start after the last start attempt Pickup Failure Unable to read the pickup signal while engine is running Output Circuit Overload Short circuit in one of the +24 volt terminals Analog Sensor Failure Detailed information on which analog channel has failed Broken Wire Detailed information on which terminal experienced the broken wire