Cummins — 3666003

C Series Generator, Main Section 21 - Main Power Generator - Group 21 Page 21-7 The following analog values are available from the classed remote panel. The following shows the commands that can be executed with the classed remote panel. The following lists the alarms shown by the Classed Remote Panel. Un-Classed Base Panel - The un-classed base panel mounts in the cabinet as shown.

Value Description Range and Units Oil Pressure 0.0 - 6.0 Bar 0 - 87 PSI Oil Temperature 0 - 150°C 32 - 302°F Coolant Temperature 0 - 130°C 32 - 266°F Battery Voltage 20 -30 Volts Engine Speed 0 - 2000 RPM Exhaust Stack Temperature 0 - 600°C 32 - 112°F Total Engine Hours 0 - 99999 Hours Trip Engine Hours 0 - 999 Hours Starter Counter 0 - 99999 Starts Command Description Engine Start Brings up a dialog to confirm engine start Engine Stop Brings up a dialog to confirm engine stop.

An ongoing start attempt can be cancelled by pressing stop Acknowledge Alarms Will acknowledge all pending alarms in the Classed Base Panel Set to Standby The Classed Base Panel will do automatic start attempts Set to Manual The Classed Base Panel will not do automatic start attempts Alarm Description Comment Low Oil Pressure 1.7 Bar [25 psi] High Coolant Temperature 106°C [223°F] Emergency Stop/Start Disabled Manual emergency stop is operated. Start is disabled.

Low Coolant Pressure 0.7 Bar [10 psi] Power Failure Either the primary or the secondary (backup) voltage supply to the DCU 305 R2 is too low Overspeed 50 Hz overspeed = 1725 RPM, 60 Hz overspeed = 2070 RPM Oil Pressure 2.4 Bar [35 psi] Oil Temperature 120°C [248°F] Coolant Temperature 104°C [219°F] Start Failure When set to Standby only.