MH MH6.6/MH8.6 — GB COPERTINA.fm

6-14 CALIBRATION MH6.6 / MH8.6 Carefully read personal and machine SAFETY INSTRUCTIONS (at the beginning of this manual) Step Display text Remarks 1 COMPLETE As an alternative to the COMPLETE selection (Fig. 2), the menus DEFAULT (Fig. 3) or indi- vidually SPOOL 1 to SPOOL 8 can be selected. On confirmation of the COMPLETE selection, the following calibration steps are executed one after another. 2 Safety lever to bottom position 1 Safety lever (72) to position 1, electrohydraulic pilot control ON 3 Close bucket Shift joystick (69) to the left (fill bucket) 4 Hold joystick imn max.

position 5 Spool 1 started 6 Calibration bottom hood spool 1 - 8 7 Measure at test point pressure xxx bars 8 Calibration top hood spool 1 - 8 9 Measure at test point pressure xxx bars 10 Joysticks and pedale to neutral position 11 Calibration sucessfully completed 12 Safety lever to top position 0 Safety lever (72) to position 0, electrohydraulic pilot control OFF 13 Calibration done Step Display text Remarks 1 DEFAULT 2 Restore default settings Successfully completed