Engine Monitoring and Protection 15.1.8.2 Auxiliary Temperature Monitoring Configuration Three parameters can be configured in Cat ET to customize the monitoring system for high auxiliary temperature monitoring. 1. ECU action for an event code defaults to “On” for Warning and “Off” for Derate and Shutdown. All actions can be configured to “On” or “Off.” 2. Time delay to take action defaults to four seconds for Warning, Derate, and Shutdown. Time delay to take action can be set between one and 120 seconds. 3. Auxiliary temperature maximum limit default for Warning is 105° C, Derate is 106° C, and Shutdown is 107° C.
The maximum temperature limit for each action can be set within the range of 0° C and 140° C. The following table summarizes the configuration default settings and configuration ranges for high auxiliary temperature monitoring: NOTE: The engine must be running at engine speeds at or above low idle for 180 seconds before the above time delay is triggered. 15.1.8.3 Auxiliary Temperature Monitoring Installation Auxiliary temperature sensor is an optional attachment. Refer to Auxiliary Temperature Sensor in the Customer Installed Components section of this document.
15.1.9 Auxiliary Pressure 15.1.9.1 Auxiliary Pressure Monitoring Operation Auxiliary pressure is monitored to automatically protect a customer-defined system from exceeding the maximum pressure limit of that system. The auxiliary pressure measured by the ECU is compared to a maximum auxiliary pressure limit configured in the monitoring system for auxiliary pressure monitoring. The maximum auxiliary pressure is checked for each ECU action level configured in the monitoring system. If the auxiliary pressure is above the maximum auxiliary pressure for the specified action level delay time, then the ECU takes the appropriate action to respond to the fault condition.
Once the fault is detected, the ECU illuminates the warning and diagnostic lamps and logs the appropriate event code from the following table for the action taken: A P P L I C A T I O N A N D I N S T A L L A T I O N G U I D E 103 HIGH AUXILIARY TEMPERATURE MONITORING CONFIGURATION Action Default Value Time Delay (sec) Set Points Range Default Range Default Warning On 1 to 120s 4 0° C to 140° C 105° C Derate Off 1 to 120s 4 106° C Shutdown Off 1 to 120s 4 107° C Cat ET Description J1939 Description Status SPN FMI High Auxiliary Pressure Auxiliary Pressure #1 Warning 1387 15 Derate 1387 16 Shutdown 1387 00