Peripheral Devices Figure 2 17.2.3.2 Instrument Panel Group J1939 Data Link The Industrial Instrument Panel Group has an internal terminating resistor on the J1939 data link. The harness assemblies listed in Table 1 also have terminating resistors. If one of these harness assemblies is used with the instrument panel, no additional termination is needed. If the harness assembly is not used, consult section 5.4.2 for instruction in J1939 data link termination. 17.2.3.3 Instrument Panel HI/LO Idle The harness assemblies listed in Table 1 provide a ground for the PTO Enable input (J1/P1 pin 56) on the engine ECU.

If the harness assembly is not used, the PTO Enable input must be grounded in order for the HI/LO Idle switch to function properly. This will also require that the PTO Ramp Up/Set and the PTO Ramp Down/Resume switch inputs be properly connected. Refer to the appropriate schematic listed in appendix A9. 17.3 Discrete Input/Output Module 17.3.1 Discrete Input/Output Module Operation The 234-0275 Discrete Input/Output (I/O) Module was primarily designed for use on generator set applications. However, it can be used on industrial engine applications to provide flexibility in system monitoring and control. The module can be used on 12V and 24V systems.

The module has 12 discrete inputs and 8 relay outputs. The 8 relay outputs are available with normally open and normally closed contacts. The 12 inputs are switch to ground inputs and the module provides 4 ground pins in the 40-pin connector. The inputs and outputs are configured using Cat Electronic technician (ET). For example, the module can be configured to activate a relay or lamp based on the status of a temperature or pressure switch. The module also can be programmed with a delay of 0 to 120 seconds between the time a condition on the input is met and when it activates an output to turn on a relay, lamp, alarm, etc. I N D U S T R I A L E N G I N E E L E C T R O N I C S 118