Connectors and Wiring Harness Requirements Figure 7: J1939 Multiple Module Installation Example Terminating Resistor (1) (174-3016) Cable (3) Maximum Length = 40 m (130 ft) (153-2707) Receptacle Tee ( 133-0970) Cable (2) Cable (3) (165-0200) P1/J1 ECM (153-2707) Cable (2) (153-2707) Cable (3) (165-0200) J1939 Module Cable (3) Cable (2) (153-2707) (165-0200) J1939 Module Terminating Resistor (1) (174-3016) (1) Two terminal resistors are required . Optional Customer Harness provides the resistor at the ECM if installed . (2) Maximum stub length = 1 m (3.3 ft) (3) Fabricate 153-2707 cable to length NOTE:
If the requirements for J1939 data link connections are met, any number of display modules or service tool connectors may be connected to the J1939 data link. NOTE: One terminal resistor for the J1939 data link is included in the optional customer harness. If the optional customer harness is not present, two terminal resistors must be installed. Any J1939 data link must have a terminal resistor at each end of the data link. NOTE: A terminal resistor is required at the terminal ends of the data link cable. A terminal resistor is not required at each node on the data link. A P P L I C A T I O N A N D I N S T A L L A T I O N G U I D E 39