Engine Speed Demand Step 4. Increase the PLC output to the maximum current (20mA) and observe the “Throttle Input Duty Cycle” value in Cat ET. Subtract 5 from this value and record the difference. This difference is the proper value for the “Throttle Input High Idle Duty Cycle” configuration parameter. • Note: This value cannot be less than 50 percent or greater than 90 percent. • Subtracting 5 provides a tolerance (deadband) for variations in the Remote Speed Control output such as small amounts of temperature-related drift. Step 5. Enter the values for the two parameters into the configuration screen in Cat ET. Note:
Placing the Remote Speed Control into Local Mode by opening switch SW1 passes control over to the 1k potentiometer (if the two inputs are within 2.5 percent of each other). Care should be taken since the range of adjustment of the potentiometer can cause the output duty cycle to fall below 5 percent or rise above 95 percent causing the desired engine speed to be set to low idle and a diagnostic to log. Step 6. For Local Mode use only (no PLC controller or switch SW1), adjust the potentiometer to end of its range to produce the minimum duty cycle on the output of the Remote Speed Control (this will log a diagnostic).
Then adjust the potentiometer a known amount away from the end of the adjustment range. For example, for a 10-turn potentiometer, adjust one or two full turns away from the end of the range. Observe the “Throttle Input Duty Cycle” status parameter in Cat ET. If the value is between 10 and 40 percent, this value can be used for the Throttle Input Low Idle Duty Cycle configuration parameter. This will allow the desired engine speed to reach low idle before the potentiometer reaches the end of its travel and helps to reduce the occurrences of diagnostic logging during adjustment.
This also helps to provide a better relationship between the amount of adjustment of the potentiometer and the duty cycle since most potentiometers have better linearity away from the end of their adjustment range. Step 7. Adjust the potentiometer to the end of its range to produce the maximum duty cycle on the output of the Remote Speed Control (this will log a diagnostic). Then adjust the potentiometer a known amount away from the end of the adjustment range. For example, for a 10-turn potentiometer, adjust one or two full turns away from the end of the range. Observe the “Throttle Input Duty Cycle” status parameter in Cat ET.
If the value is between 50 and 90 percent, the value can be used for the Throttle Input High Idle Duty Cycle configuration parameter and will allow the desired engine speed to reach high idle before the potentiometer reaches the end of its travel. This also helps to reduce the occurrences of diagnostic logging during adjustment. Note: Outside of the programmable limits discussed previously, there are no hard and fast rules as to what the values should be for the two configuration parameters. It becomes more of a judgment call depending on the type of potentiometer used and the resolution desired. Step 8. Enter the values for the two parameters into the configuration screen in Cat ET.
Clear the logged diagnostics created during this procedure. I N D U S T R I A L E N G I N E E L E C T R O N I C S 64