Cooling System QSB4.5 and QSB6.7 Page 5-4 Section 5 - Maintenance Procedures at 500 Hours or 6 Months Flush The system must be filled properly to prevent air locks or serious engine damage can result. During filling, air must be vented from the engine coolant passages. Wait 2 to 3 minutes to allow air to be vented; then add mixture to bring the level to the top. CAUTION To be sure air is vented during the fill process: Some thermostat have check balls that allow air to vent through the thermostat when the thermostat is closed. An air vent port connection, which connects to the top tank/coolant recovery tank of the cooling system, is located next to the water outlet.
This provides adequate venting for a fill rate of 19 liters [5 gal] per minute. NOTE: An alternate to using sodium carbonate, as outlined in this procedure, is to use Restore™. Restore™ is a heavy-duty cooling system cleaner that removes corrosion products, silica gel, and other deposits. The performance of Restore™ is dependent on time, temperature, and concentration levels. An extremely scaled or flow-restricted system, for example, can require higher concentrations of cleaners, higher temperatures, longer cleaning time, or the use of Restore Plus™. Up to twice the recommended concentration levels of Restore™ can be used safely.
Restore Plus™ must be used only at its recommended concentration level. Extremely scaled or fouled systems can require more than one cleaning. NOTE: Do not install the radiator cap. The engine is to be operated without the cap for this process.