Komatsu PC210-8, PC210LC-8, PC210NLC-8, PC230NHD-8, PC240LC-8, PC240NLC-8 — Electrical control system

10 Structure, function and maintenance standard UEN00103-00 1) Function to control pump during travel q For details, see Engine and pump composite control function. 2) Travel speed change function 1] Manual change with travel speed selector switch Switching the travel speed selector switch from Lo to Mi and Hi causes the pump controller to control the pump capacity and motor capacity at each gear speed as shown below, switching the travel speed. 2] Automatic change by engine speed If you adjust the engine speed to 1,500 rpm or less with the fuel control dial, q The travel speed does not switch to Hi when the machine is travel- ing in Mi.

q The travel speed automatically changes to Mi when the machine is travelling in Hi. 3] Automatic change by pump discharge pressure If the travel pressure is kept to 24.5 MPa {250 kg/cm 2 } at least 0.5 sec. due to increased load during traveling in Hi on an uphill, the travel motor capacity automatically switches to the medium speed (Mi) (the travel speed switch stays at Hi). If the machine starts traveling on level ground or downhill during operation of the above mentioned function and the travel pressure goes below 14.7 MPa {150 kg/cm 2 } and continues such the condition at least 0.5 sec., the travel motor capacity will automatically change, switching the travel speed switch to Hi again.

PC210, 230, 240-8 25 Travel speed switch Lo (Low speed) Mi (Medium speed) Hi (High speed) Pump capacity (%) 80 90 100 Motor capacity Max. Max. Min. Travel speed (km/h) 3.0 4.1 5.5