UEN00244-00 40 Troubleshooting 54 PC210, 230, 240-8 Trouble (13) Air conditioner abnormality record: Refrigerant “Abnormality” Related infor- mation • If “CAN disconnection” is displayed as communication condition, communication cannot be carried out normally. Accordingly, this condition is not displayed. • Method of reproducing abnormality record: Turn starting switch ON + Turn air conditioner (A/C) switch ON. Possible causes and standard value in normal state Cause Standard value in normal state/Remarks on troubleshooting 1 Insufficient refrigerant (gas) (when system is normal) Refrigerant (gas) may be insufficient. Check it directly.
2 Defective high and low pres- sure switches (Internal dis- connection) a Prepare with starting switch OFF, then carry out troubleshooting without turning starting switch ON. P17 (male) Resistance Between (1) – (2) Max. 1 z 3 Disconnection in wiring har- ness (Disconnection in wiring or defective contact in con- nector) a Prepare with starting switch OFF, then carry out troubleshooting without turning starting switch ON. Wiring harness between ACW (wiring side) (4) – P17 (female) (1) Resis- tance Max. 1 z Wiring harness between P17 (female) (2) – chassis ground (T06) Resis- tance Max.
1 z 4 Defective air conditioner con- troller If causes 1 – 3 are not detected, air conditioner controller may be defective. (Since trouble is in system, troubleshooting cannot be carried out.)