OPERATION 3.4 ELECTRONIC MONITORING AND CONTROL SYSTEM ECS Menu Control with Switch (C) and Key Group (D) Display of DIGITAL-OUTPUTS Example: You want to display the condition of the Pump Regu- lation Valve (Qmin) Y17 in the group *DIGITAL-OUTPUTS*, starting from menu level -2-, see Control Chart V. Proceed as follows: 1. Starting from level -2- *ANALOG-INPUTS* press key (12) twice, the display changes to *DIGITAL-OUTPUTS*: 2. Press ”QUI” key (10) the starting menu item ”H22 ACOUSTIC SIGNAL* in level -3- appears on the display, see chart V. 3. Press key (12) until the menu item *Y17 PUMP REGULA- TION QMIN* is displayed. 4. Press key (10).
Depending on the Operating Condition of the hydraulic system, one of the two following displays (A or B) in level -4- appears on the screen. A – Display with main pumps in Qmin position, pause switch- ing active and hydraulic oil cooler fans not running -4- Pump regulation Qmin | 0 | 1 | Y17 ( A1.4): 1 B – Display with hydraulic oil at operating temperature, hydraulic oil cooler fans running and pause switching inac- tive -4- Pump regulation Qmin | 0 | 1 | Y17 ( A1.4): 0 5. For display of further solenoid valve or relay settings go back to level -3- by pressing ”RET” key (9). Use key (12 or 11) to select those items you want to be displayed.
Press key (10) for display of settings in level -4-. 6. For returning to the basic display in level -0- press key (9) four times. DO NOT change any settings in the INPUT-OUTPUT groups before having the permission of authorized Service Staff. 149 CAUTION CAUTION