Caterpillar — cat.com

G E N E R A T O R S GENERATOR ANTI-CONDENSATION HEATER AH1H Appropriate when the generator set is to be sited in a low ambient and/or high humidity environment, the heater maintains the AC generator at a suitable temperature to prevent winding corrosion due to condensation. The heater itself is powered by a 110/120 volt (VAC 120) or 208/240 volt (VAC 240) AC auxiliary supply protected by a fuse inside the main control panel. When the generator set is not running the heater is automatically connected to the AC supply through a power relay mounted in the control panel.

Upon receiving a start signal the AC supply is automatically disconnected by the power relay and automatically reconnected when the start signal is removed and the engine has stopped. www.cat-ElectricPower.com Market: N. America Information contained in this publication may be considered confidential. © 2005 Caterpillar LEHE4017 (01-05) Discretion is recommended when distributing. All Rights Reserved. Materials and specifications are subject to change without notice. Printed in U.S.A. 24