hitachi — OTHER SYSTEM TROUBLESHOOTING

TROUBLESHOOTING / Troubleshooting B Cooling Circuit T5-7-144 Refrigerant pressure Bubbles can be seen in sight Piping and/or parts are stained with oil, in both high and glass. respond to gas detector. low-pressure sides is low. No oil stain is found or gas detector does not respond. Refrigerant has not been refilled for longer than one sea- son. No bubbles are seen in sight glass. After cooling at fast speed continu- ously, cooling power is reduced. Air flow volume remains unchanged. Air flow volume is reduced. Refrigerant pressure in low-pressure side Bubbles can be seen in sight Compressor cylinder is extremely hot, Insuffi- is high. glass. emitting a smell.

cient Cooling Power Refrigerant pressure in Compressor cylinder is extremely hot, high-pressure side is low. emitting a smell. Heater unit emits hot air. Refrigerant pressure in high-pressure side Bubbles can be seen in sight Refrigerant pressure in low-pressure is high. glass. side is low. Condenser is stained and clogged. Even if condenser is sprayed with water, few bubbles appear. Receiver dryer tem- perature is low. After cooling at fast speed continu- ously, cooling power is reduced. Air Frost forms. Thermistor does not cool. flow volume is reduced. Thermistor cools. Thermistor cools.