hitachi — OTHER SYSTEM TROUBLESHOOTING

TROUBLESHOOTING / Troubleshooting B Compressor Compressor does not rotate. Clutch terminal voltage is normal 24 V. Inoperable cooling system. Clutch terminal voltage is low. Clutch terminal voltage is 0 V. Bubbles exist even after refrigerant is refilled. Both high and low side pressures are low. Check for oil and refrigerant leaks from parts other than compressor and pipe joints by using gas detector. Both com- pressor and blower mo- tor rotate. Check for oil and refrigerant leaks from compressor (no leaks from parts other than compressor) by using gas detector. (Refer to NOTE 1, 2 on page T5-7-151.) Stain on exterior. Refrigerant has not been refilled for longer than one season.

Refrigerant is discharged within 1 to 2 months after being recharged. Check for refrigerant leaks using gas detector. Refrigerant is kept charged for longer than 2 years. High pressure side is slightly low and low pres- sure side is high. Compressor cylinder is not hot. (Refrigerant returns to com- pressor in liquid form.) No refrigerant returns in liquid form. High pressure side is low. Bubbles can be seen through sight glass. Others High pressure side is high. Refer to the Cooling Circuit Troubleshooting Table on page T5-7-136. Temperature is not cooled when compressor is operated at fast speed continuously. Air flow from blower is insufficient. T5-7-148