John Deere 450DLC — Travel Alarm Circuit Theory of Operation

Sub-System Diagnostics The travel alarm circuit is designed to warn bystanders of machine movement by signaling with an audible alarm any time the travel levers are moved. The travel alarm circuit consists of the following components: and send signals to the MCF. The MCF then sends a signal to the travel alarm (H4), activating the alarm. Pushing travel alarm cancel switch (S13) applies ground to pin 4 of the travel alarm. The travel alarm cancel switch must be pushed and released in order to cancel the alarm. The travel alarm will be active for a minimum of 13 seconds before the travel alarm cancel switch can deactivate it.

The travel alarm is reset when the travel levers are returned to the neutral position. The travel alarm cancel switch must be pushed and released again to cancel the alarm. Travel right pressure sensor (B56) Travel left pressure sensor (B57) Travel alarm (H4) Main controller (MCF) (A3) Travel alarm cancel switch (S13) When the travel levers are moved, travel right and left pressure sensors (B56 and B57) sense pilot pressure LD30992,0000214 –19–19APR06–2/2 9015 15 36 TM2361 (24JUN08) 9015-15-36 450DLC Excavator Operation and Tests 062608 PN=480